Technical Data:
1.Outdoor use
2.Cast-resin insulated
3.Frequency 50Hz or 60Hz
4.Rated insulation level: 17.5/38/95kV
5.Standards: IEC 60044-1&2 IEC 61869-1&2&3
The transformer is casted together by 1 CT and 1 PT with small size, it saves room. It can be used outdoor, Its highest voltage for equipment can be 17.5kV.
|
Rated primary Voltage
(kV)
|
Rated secondary
Voltage
(kV)
|
Accuracy classes
|
Rated output(VA)
|
Rated current ratio
(A)
|
Accuracy class
|
Rated output
|
Rated Insulation level
(kV)
|
|
10/√3
11/√3
12.47/√3
13.8/√3
15/√3
|
100/√3
110/√3
120/√3
100
110
120
|
0.2
0.5
1
|
10
30
50
|
5-10/5
|
0.2S
0.2
0.5S
0.5
1
|
10
12.5
15
|
12/28/75
12/42/75
17.5/38/95
17.5/38/110
15/34/110
|
|
10-20/5
|
|
15-30/5
|
|
….
|
|
200-400
|
|
300-600
|
|
400-800
|
|
500-1000
|
|
600-1200
|
Outline drawing: