Main
technical parameter
1. Rated
voltage : 66kV or 69kV
2. Highest
voltage for equipment : 72.5 kV
3. Rated
insulation level : 72.5/140/325kV
4. Rated
secondary current :5Aor1A
5. Standards: IEC60044-1.2003 Part 1: Instrument transformers-Part1: Current
transformers or ANSI IEEE STD
C57.13-2008
6. Other
technical parameter pls see as follow:
|
Rated Transformation ratio(A)
|
Secondary accuracy classes combination
|
Rated output
(VA)
|
Rated
short-time thermal current (kA/1s)
|
Rated
dynamic current ( kA)
|
|
Measuring
|
Protective
|
|
0.2S
|
0.5
|
10P15
|
|
25~200/5
|
0.2S/0.5/10P15
0.2/0.5/10P15
0.2S/10P15/10P15
0.2/10P15/10P15
|
50
30
|
50
30
|
50
30
|
150I1n
|
375I1n
|
|
300/5
|
42.5
|
100
|
|
400/5
|
50
|
100
|
|
500/5
|
63
|
125
|
|
600/5
|
80
|
125
|
|
750/5
|
80
|
125
|
|
800/5
|
100
|
160
|
|
1000~1500/5
|
100
|
160
|
Double ratios
|
Rated Transformation ratio(A)
|
Secondary accuracy classes combination
|
Rated output
(VA)
|
Rated short-time
thermal current (kA/1s)
|
Rated dynamic
current Idyn( kA)
|
|
Measuring
|
Protective
|
|
0.2
Tap
|
0.2S
Full
|
0.5
|
10P15
|
|
2X25/5
|
0.2S/0.5/10P15
0.2/0.5/10P15
0.2S/10P15/10P15
0.2/10P15/10P15
|
30
|
50
30
|
50
30
|
50
30
|
2X3
|
2X8
|
|
2X50/5
|
2X6
|
2X15
|
|
2X75/5
|
2X 9
|
2X22.5
|
|
2X100/5
|
2X 12
|
2X30
|
|
2X150/5
|
2X15
|
2X37.5
|
|
2X200/5
|
2X 22.5
|
2X56
|
|
2X300/5
|
2X 31.5
|
2X80
|
|
2X400/5
|
2X 42.5
|
2X100
|
|
2X600/5
|
2X 55
|
2X137.5
|
|
2X750/5
|
2X 70
|
2X175
|
Remarks: Upon request we are
glad to offer transformers according to other standards or with non-standard
technical specs.
Outline drawing