Main technical
parameter
1. Rated voltage: 11kV or 13.8kV or 15kV
2. Rated secondary current:5Aor1A
3. Standards: IEC60044-1.2003 Part 1: Instrument transformers-Part1: Current
transformers
4. Other technical parameter pls see as follow:
|
Rated primary
current (A)
|
Secondary
accuracy classes combination
|
Rated output
(VA)
|
Rated short-time thermal current (kA/S)
|
Rated dynamic current ( kA)
|
|
0.2(S)
|
0.5
|
10P
|
|
50-200/5
|
0.2(S)/0.2(S)
0.2(S)/0.5
0.2/(S)10P
0.5/10P
0.2S/0.5/10P
0.2/0.5/10P
|
10
15
|
15
|
15
20
|
150I1n
|
375I1n
|
|
300/5
|
31.5
|
80
|
|
400/5
|
31.5
|
80
|
|
500/5
|
40
|
100
|
|
600/5
|
50
|
125
|
|
800/5
|
63
|
125
|
Remarks: Upon request we are glad to
offer transformers according to other standards or with non-standard technical
specs.
Outline drawing